Nút nhấn khẩn GST DC-9204E
- DC-9204E Innovation Manual Call Point (MCP) is non-addressable. It alarms by the output current. It can be simply connected to compatible conventional fire alarm system from various manufacturers. The MCP is suitable for public places. When there is a fire, pressing the frangible element on the MCP can send fire signal to fire alarm control panel.
Specifications
Model |
DC-9204E |
Operating Voltage |
24VDC (12~28VDC) |
Standby Current |
0mA |
Alarm Current |
≤30mA (equivalent resistance is 470Ω 1/2W) |
Indicator |
Red. Illuminates after alarming. |
Type of Initiating Part |
Reusable |
Initiating Mode |
Pressing the frangible element manually |
Resuming Mode |
Manually resumed by a special key |
Wiring |
two-wire |
Class |
Type A, indoors |
Ingress Protection Rating |
IP43 |
Environmental Temperature |
-10℃~+55℃ |
Relative Humidity |
≤95%, non-condensing |
Material of Enclosure |
ABS, red |
Dimension (L×W×H) |
87.1×87.1×58.5 mm (with back box) |
Mounting Hole Distance |
60mm |
Weight |
About 160g (with back box) |